pre-configured control panels

H2flow pre-configured control panels are engineered to exacting standards and feature UL 508 and UL 698 certification. Every panel is manufactured using only the highest quality materials at our facility in Sylvania, Ohio.  

Types of pre-configured control panels offered:

  • DCM Simplex ATL, NEMA 4 or NEMA 4X, for floatless control of a simplex submersible pump application with across-the-line starting.
  • DCM Duplex ATL, NEMA 4 or NEMA 4X, for floatless control of a duplex submersible pump application with across-the-line starting.
  • DCM Simplex Soft Start, NEMA 4 or NEMA 4X, for floatless control of a simplex submersible pump application with use of a Soft Start.
  • DCM Duplex Soft Start, NEMA 4 or NEMA 4X, for floatless control of a duplex submersible pump application with use of a Soft Start.
  • ATL Simplex float control, NEMA 4 or NEMA 4X, for across-the-line starting of a simplex submersible pump application.
  • ATL Duplex float control, NEMA 4 or NEMA 4X, for across-the-line starting of a duplex submersible pump application.
  • Soft Start Simplex float control, NEMA 4 or NEMA 4X, for simplex control of a submersible pump application with use of a Soft Start.
  • Soft Start Duplex float control, NEMA 4 or NEMA 4X, for duplex control of a submersible pump application with use of a Soft Start.

 

Don't see a panel that meets your requirements? Contact us to speak to an experienced H2flow representative about how we can assist you with your motor control panel needs.

 

advantages of h2flow control panels

>ROBUST CONSTRUCTION H2flow control panels are built to exacting standards and feature UL 508 and UL 698 certifications.

>ROBUST CONSTRUCTION

H2flow control panels are built to exacting standards and feature UL 508 and UL 698 certifications.

>ADVANCED FUNCTIONALITY Panels from H2flow that include Emotron VFDs and Soft Starts feature advanced communication and software options.

>ADVANCED FUNCTIONALITY

Panels from H2flow that include Emotron VFDs and Soft Starts feature advanced communication and software options.

>SUPPORT All H2flow control panels include first-class service and support.

>SUPPORT

All H2flow control panels include first-class service and support.


“We have never received panels of this quality and will continue to use H2flow Controls for all of our future needs.”
— Scott E., Washington, PA

sensorless level control

DCM panels from H2flow eliminate the maintenance issues associated with floats in submersible pump applications.

Using the Emotron Drainage Control Monitor (DCM), H2flow control panels for submersible applications eliminate all but the 'high / high' float.

The unique timing algorithms of the DCM constantly adapt the pumps pause time before automatically switching on for the next pump-down cycle. In duplex applications, the DCM will also provide pump alternation after each cycle. In the event of a sudden in-rush of fluid into the sump, the high / high float will signal the DCM to override its calculated pause time and turn the pump on.

key features

  • NEMA 4 or NEMA 4X enclosure
  • Main incoming line circuit breaker disconnect with thru-door-disconnect handle mechanism
  • IEC-rated Across-The-Line contactor with electronic thermal overload relay
  • Control power transformer with dual primary and single secondary fusing
  • Emotron Drainage Control Monitor for pump control
  • Hand-Off-Auto selector switch
  • Alarm pilot light (red)
  • Alarm reset pushbutton
  • Run pilot light (green)
  • Customer terminal blocks including temp and seal leak
  • Wiremarkers, electrical schematics